Product selector

800 Series

800 Series

High-level/overdoor heaters

SCH

SCH

Suspended ceiling heaters

CHS

CHS

Suspended ceiling multi-heater systems

RH

RH

Recessed ceiling heaters

OUH

OUH

Industrial Unit heaters wall-mounted

DSU series

DSU series

Destratification units

WHE

WHE

Compact heavy-duty wall heaters

OUH

Unit Heaters

  • Providing an efficient means of heating large industrial premises
  • Exceptional reliability – backed by 5 year warranty
  • The most robust industrial unit heater available

Typical Applications

  • Warehouses
  • Workshops

The installed load must exceed the heat loss from the entire area. OUH unit heaters are space heaters – they are NOT suitable for ‘spot heating’.

Features Common to all Models

  • FIVE YEAR WARRANTY
  • Integral contactor and fused control circuit
  • Heavy gauge steel construction with almond (RAL9001) finish
  • Adjustable louvers
  • Wall and ceiling brackets supplied as standard
  • Optional suspension kit (OUH-J)
  • Optional diffuser (OUH-CD) for use with suspended heaters; aids air circulation
  • Optional factory fitted built-in thermostat (OUH-TH-16)
  • Terminals supplied for easy connection to remote control devices
  • Auto-reset over-temperature protection

Controlling OUH Heaters

OUH heaters are best controlled using a tamperproof Electronic Control Device from BN Thermic’s Hard Case range.  Hard Case’s tamperproof design ensures that only authorised personnel can adjust the temperature setting.

Each heater will be controlled by an individual Hard Case Electronic Control Device generally mounted immediately below the heater at approximately 1.5m above floor level.  This is an energy saving approach allowing the control system to take into account differing conditions in different parts of the building.  The use of dedicated electronic control devices also keeps installation time to a minimum.

We offer 3 control packages

Standard Control Package
Programmable Package
Programmable Package with Set-Back

Standard Control Package
  • Control is by means of a Hard Case HC-T2 Tamperproof Electronic Control Device
  • Access to temperature adjustment requires an HC-D tool ensuring that only authorised personnel can adjust settings
  • An integral switch allows authorised personnel to select between two temperature scales: 0-12⁰C for frost protection or 12-25⁰C for comfort heating.
Components

HC-T2 Hard Case Tamperproof Electronic Control Device (one per heater)
HC-D Hard Case Tool (required to access temperature settings)

Programmable Package
  • Control is by means of a Hard Case HC-T2 Tamperproof Electronic Control Device
  • Access to temperature adjustment requires an HC-D tool ensuring that only authorised personnel can adjust settings
  • An integral switch allows authorised personnel to select between two temperature scales: 0-12⁰C for frost protection or 12-25⁰C for comfort heating.
  • A TIM-D1 24 hour/7 day programmable timer will ensure that the heating system is not energised while the building is unoccupied (typically at night and at weekends).
  • The programmable timer has a built-in run-down clock that is triggered by the TIM-B1 remote mounted ‘boost button’.  This feature will provide a temporary temperature boost for a pre-determined length of time during a period when the system would normally be ‘off’.  The boost command can be cancelled by depressing the ‘boost button’ for 3 seconds.
Components

HC-T2 Tamperproof Electronic Control Device (one per heater)
HC-D - Hard Case Tool (required to access temperature settings)
TIM-D1 Programmable Timer
TIM-E1 Timer Enclosure
TIM-B1    Boost Button

Programmable Package with Set-Back
  • Control is by means of a Hard Case HC-ST2 Tamperproof Electronic Control Device
  • Access to temperature adjustment requires an HC-D tool ensuring that only authorised personnel can adjust settings
  • The HC-ST2 has two adjustable settings: high (comfort) and low (set-back).
  • A TIM-D1 24 hour/7 day programmable timer will ensure that the heating system operates at its low (set-back) setting while the building is unoccupied (typically at night and at weekends).
  • The programmable timer has a built-in run-down clock that is triggered by the TIM-B1 remote mounted ‘boost button’.  This feature will provide a temporary temperature boost for a pre-determined length of time during a period when the system would normally be in set-back mode.  The boost command can be cancelled by depressing the ‘boost button’ for 3 seconds
Components

HC-ST2 Tamperproof Electronic Control Device with Set-Back (one per heater)
HC-D - Hard Case Tool (required to access temperature settings)
TIM-D1 Programmable Timer
TIM-E1 Timer Enclosure
TIM-B1    Boost Button
 

Specification

Model Output
(kW)
Volts Airflow
(m3/h)
Dimensions (mm) Recommended
Mounting
Height(m)
Weight
(kg)
H W D
OUH-03-1 3.0 230/1 1180 305 420 432 2.5 23
OUH-03-3 3.0 400/3N 1180 305 420 432 2.5 23
OUH-05-1 5.0 230/1 1180 305 420 432 2.5 23
OUH-05-3 5.0 400/3N 1180 305 420 432 2.5 23
OUH-07-1 7.0 230/1 1180 305 420 432 2.5 23
OUH-07-3 7.0 400/3N 1180 305 420 432 2.5 23
OUH-10 10 400/3N 1180 305 420 432 2.5 23
OUH-15 15 400/3N 2200 444 560 572 3.0 35
OUH-20 20 400/3N 2200 444 560 572 3.0 35
OUH-25 25 400/3N 2200 444 560 572 3.0 35
OUH-TH-16 Optional factory fitted thermostat 0.3
OUH-J J hooks for vertical suspension (set of 4) 2.0
OUH-CD1 Diffuser for suspended heater 3kW to 10kW 4.0
OUH-CD2 Diffuser for suspended heater 15kW to 25kW 7.0
OUH Unit Heaters

OUH Unit Heaters

OUH Optional Diffuser for vertical suspension

OUH Optional Diffuser for vertical suspension

Mounting options with brackets provided

Mounting options with brackets provided

Standard Control Package

Standard Control Package

Programmable Package

Programmable Package

Programmable Package with Set-back

Programmable Package with Set-back