Product selector
CRJ
Self Regulating Water Pipe Freeze Protection Cable
- Prevents water from freezing in metal and plastic pipes
- Avoids the cost and inconvenience of burst pipes
- Self regulating technology and recommended thermostatic control ensures lowest possible running costs
Typical Applications
- Stables
- Sprinkler systems
Features
- Self regulating technology ensures that cable output will decrease as ambient temperature increases
- Can be cut to length, terminated, T jointed and spiced on site using the BN Thermic’s termination and splice kits
- Can be double wrapped to protect valves, flanges etc. without risk of creating hot spots
- Fully moisture proof with full length earth braid
Controlling CRJ Self Regulating Pipe Freeze Protection cable
Although the cable’s self regulating technology ensures that cable output will decrease as ambient temperature increases, thermostatic control is still recommended. A master frost thermostat will prevent the low level of electricity consumption that would otherwise occur when the ambient temperature was above freezing point.
BN Thermic offers a choice of two frost thermostats: FST-IN and FST-EX. The FST-EX should be selected for outdoor applications or where a tamperproof device is preferred. Both thermostats have a switching capacity of 10A. Larger loads can be switched via a suitably rated contactor.
Specification
| Model | Volts | W/m | Description |
|---|---|---|---|
| CRJ-10 | 230 | 10 | 10W/m cable - by the metre |
| CRJ-25 | 230 | 25 | 25W/m cable - by the |
| CRJ-T1 | Termination kit | ||
| CRJ-T5 | Termination kit pack of 5 | ||
| CRJ-S | Splice/Tee kit | ||
| PF-L | Caution labels - pack of 10 | ||
| PF-T | Flame Retardant fixing tape 33m x 19mm | ||
Notes on Selection and Installation
- Use the following tables to select the correct output and length of cable required for your application. You will notice that in most instances a straight run of cable will suffice. The table also indicates the thickness of the insulation which should cover both pipe and cable.
- A CRJ-T1 termination kit will be required per circuit with one CRJ-S splice kit required for every splice or T
- Secure the cable to the pipe at 200mm intervals using PF-T fixing tape
- Plastic pipes should be wrapped in AL50 aluminium tape before installing the cable
-
Maximum circuit lengths are as follows:
CRJ-10: 205m
CRJ-25: 126m - BN Thermic PF-L warning labels should be applied to the outside of the insulation
CRJ Selection Table 1
(minimum ambient temperature -20°C)
|
Pipe Dia.(mm) |
Insulation Thickness(mm) | ||
|---|---|---|---|
| 12 | 25 | 50 | |
| 12 | CRJ-10 Straight | CRJ-10 Straight | CRJ-10 Straight |
| 25 | CRJ-25 Straight | CRJ-10 Straight | CRJ-10 Straight |
| 50 | CRJ-25 Straight | CRJ-10 Straight | CRJ-10 Straight |
| 75 |
CRJ-25 1.3m cable / 1m pipe |
CRJ-25 Straight | CRJ-10 Straight |
| 100 |
CRJ-25 1.8m cable / 1m pipe |
CRJ-25 Straight | CRJ-25 Straight |
| 150 |
CRJ-25 3m cable / 1m pipe |
CRJ-25 1.4m cable / 1m pipe |
CRJ-25 1.2m cable / 1m pipe |
CRJ Selection Table 2
(minimum ambient temperature -20°C)
|
Pipe Diameter (mm) |
Additional Cable Length (m) | ||
|---|---|---|---|
|
Pair of Flanges |
Valve | Support | |
| 12 | 0.23 | 0.10 | 0.10 |
| 25 | 0.28 | 0.15 | 0.10 |
| 50 | 0.30 | 0.30 | 0.15 |
| 75 | 0.45 | 0.40 | 0.15 |
| 100 | 0.60 | 0.50 | 0.20 |
| 150 | 0.80 | 0.60 | 0.25 |
Breaker Selection for CRJ Self Regulating Cable
| Breaker | Cable Length (m) | |
|---|---|---|
| CRJ-10 | CRJ-25 | |
| 10A | 1 to 116 | 1 to 60 |
| 13A | 116 to 150 | 60 to 78 |
| 16A | 150 to 205 | 78 to 88 |
| 30A | - | 88 to 126 |
Use type C breaker
Thermostats
FST thermostats can switch up to 116m of CRJ-10 and up to 60m of CRJ-25. Longer lengths can be switched via a suitably rated contactor.