CON-32 Contactor
- Allows a thermostat or other switching device to switch loads greater than its normal capacity
- Can be used for either single phase or three phase loads
- Optional enclosure available
Range
Model |
Poles |
Amps per Pole |
Max kW per Pole @230V |
CON-32 |
3 |
32 |
7 |
CON-50 |
3 |
50 |
11.5 |
CON-80 |
3 |
80 |
18 |
ENCL-D |
Enclosure for CON-32 and CON-50 |
Selection
A contactor will allow a switching device such as a thermostat, timer or movement sensor to control a heater with a load greater than the devices switching capacity. As all the contactors in the BN Thermic range are ‘three-pole’ they will also enable a single pole device to switch a three phase load.
Using the following table, it is easy to select the contactor capable of switch any given load.
Model |
Poles |
Amps per Pole |
Max kW per Pole @230V |
CON-32 |
3 |
32 |
7 |
CON-50 |
3 |
50 |
11.5 |
CON-80 |
3 |
80 |
18 |
ENCL-D |
Enclosure for CON-32 and CON-50 |
CAUTION
When selecting a contactor to switch halogen heaters, the contactor should be over-rated by 100%
When working with voltages other than 230V 1ph or 400V 3ph & N, please consult BN Thermic
Examples
Using a 10A thermostat to switch a 4kW 230V 1ph underfloor heating mat
The 4kW mat will draw a nominal 17A. As the mat is operating on a single phase, the load will be switched using a single pole. Therefore we can select the CON-32 which is capable of switching up to 32 A per pole.
Using a 10A thermostat to switch a 30kW 4000V 3ph & N heating system.
The 30kW heating system will draw a nominal 44A per phase. As the system is operating on all three phases, the load will be switched using all three poles. We would therefore select the CON-50 which is capable of switching up to 50A per phase.