HN-1500G

HN-3000G

HN-4500G

h series halogen heaters installed in aircraft hangar
H Series
Halogen heaters
Application
Halogen heaters emit short wave radiant energy that passes through the air with minimal losses and is converted to warmth when absorbed by a solid body. They also deliver 100% of their output the instant they are energised. These characteristics make halogen heaters ideal for heating infrequently used areas or areas in which it is not practical to build up a body of warm air. Typical applications include community halls, workshops and loading bays.
Features common to all models
- Gold lamp with soft pink glow
- Built-in protective guard
- Robust aluminium case
- Bracket for wall mounting
Specification
| Model | Output (kW) |
Volts | Dimensions (mm) | Weight (kg) |
||
|---|---|---|---|---|---|---|
| H | W | D | ||||
| HN-1500G | 1.5 | 230 | 275 | 430 | 140 | 3.8 |
| HN-2000G | 2.0 | 230 | 275 | 430 | 140 | 3.8 |
| HN-3000G | 3.0 | 230 | 430 | 430 | 140 | 5.5 |
| HN-4500G | 4.5 | 230/400 3N | 590 | 430 | 140 | 6.5 |
| HN-6000G | 6.0 | 230/4003 N | 590 | 430 | 140 | 6.5 |
Options
- Kit to allow heaters to be suspended from chains. Ref. HSK
- Passive infrared movement detector. Ref. WH-402
- Combined dimmer and on/off switch. Ref. VR1
- Electronic switch timer.Ref. TS-2
Heat Requirements
Use Table 1 to determine the total kW output required. The W/m2 applicable to the type of activity and the nature of the building should be multiplied by the total area in m2. The ‘spot heating’ figure should be used when heating a section of an otherwise unheated building.
The output, position and mounting height of the heaters can be determined using
Table 2. We suggest that the areas covered by individual heaters are allowed to overlap by 10% to 15% to ensure even coverage.
| W/m2 required | |||
|---|---|---|---|
| Heavy Work |
Light Work |
Spot Heating |
|
| Highly insulated | 150 | 200 | 250 |
| Insulated | 175 | 225 | 250 |
| Un-insulated | 200 | 250 | 275 |
| Light cladding | 250 | 300 | 300 |
| Badly insulated/damp | 300 | 300 | 300 |
Spot Heating
As an additional guide to spot heating, we would also recommend heating from two directions, to cover the area from opposite sides. This will ensure an overall feeling of comfort and warmth. A heat loading of 250 - 300 W/m2 can be considered as a guide for this type of area.
| Wall Mounted (m) | Area Covered (m2) |
Overhead Mounted (m) |
Area Covered (m2) |
||||||
|---|---|---|---|---|---|---|---|---|---|
| H | X | Y | Z | H | X | Y | |||
| HN-1500 or HN-2000 |
2.5 3.0 |
3.2 3.4 |
2.6 3.6 |
6.0 6.7 |
11.9 18.2 |
3.0 3.5 |
3.0 3.3 |
2.0 2.3 |
6.0 7.6 |
| HN-3000 | 3.0 3.5 |
3.7 4.0 |
3.6 4.2 |
7.0 7.9 |
19.2 25.0 |
3.5 4.0 |
3.3 5.0 |
2.6 3.1 |
8.6 15.5 |
| HN-4500 or HN-6000 |
3.5 4.0 |
4.0 4.3 |
4.2 4.5 |
8.1 8.4 |
25.4 28.6 |
4.0 5.0 |
5.0 5.3 |
3.4 3.7 |
17.0 19.6 |