XB
ATEX Approved EExd Convector Heaters
Application
The unique compact design of the XB range makes it the ideal choice for providing heat in hazardous area installations where space is at a premium. These will include workshops and storage areas where potentially explosive gasses may be present.
All heaters in the XB range are suitable for installation in Zone 1 and Zone 2 areas and for Gas Groups IIA, IIB and IIC.
The range includes heaters stamped T3 and heaters stamped T4. Heaters stamped T3 can be installed in areas designated T1, T2 or T3. Heaters stamped T4 can be installed in areas designated T1, T2, T3 or T4.
Features
- ATEX certified
- Extended surface area black anodised copper free aluminium heat emitter with
nickel-plated guard - Universal support bracket for wall or floor mounting
- Slide out terminal block trolley simplifies installation and servicing
Specification
| Model | Temperature Class |
Output (kW) |
Volts | H | W | D | Weight (kg) |
Fig |
|---|---|---|---|---|---|---|---|---|
| XB1-3040T3BCE-11 | T3 | 0.40 | 110 | 424 | 184 | 205 | 6.8 | 1 |
| XB2-4084T3BCE-11 | T3 | 0.84 | 110 | 594 | 410 | 205 | 18.1 | 2 |
| XB3-4126T3BCE-11 | T3 | 1.26 | 110 | 594 | 635 | 205 | 27.2 | 3 |
| XB1-3043T3BCE-14 | T3 | 0.44 | 230 | 424 | 184 | 205 | 6.8 | 1 |
| XB2-6078T4BCE-14 | T4 | 0.78 | 230 | 765 | 410 | 205 | 22.7 | 2 |
| XB2-4092T3BCE-14 | T3 | 0.92 | 230 | 594 | 410 | 205 | 18.1 | 2 |
| XB3-4138T3BCE-14 | T3 | 1.38 | 230 | 594 | 635 | 205 | 27.2 | 3 |
| XB3-4230T3BCE-14 | T3 | 2.30 | 230 | 594 | 635 | 205 | 27.2 | 3 |
| XB3-6276T3BCE-14 | T3 | 2.75 | 230 | 765 | 635 | 205 | 34 | 3 |
| XB3-4138T3BCE-37 | T3 | 1.38 | 400/3 | 594 | 635 | 205 | 27.2 | 3 |
| XB3-4230T3BCE-37 | T3 | 2.30 | 400/3 | 594 | 635 | 205 | 27.2 | 3 |
| XB3-6276T3BCE-37 | T3 | 2.75 | 400/3 | 765 | 635 | 205 | 34 | 3 |
Control options
- Built-in externally adjustable thermostat directly switching all heaters in the XB range including three phase models (add suffix ‘T’)
- ATEX certified wall mounted thermostat directly controlling single phase loads up to 16 amps. Larger loads and three phase loads can be controlled via a suitably rated contactor. When controlling heaters installed in a hazardous area it is common practice to locate the contactor in a safe area. In this way the cost of an EExd enclosure to house the contactor is avoided. Ref. BNEX-1
Other options
- UL listed and CSA certified models available (consult our Sales Office)
Figure 1L |
184mm |
Figure 2 |
410mm ![]() |
Figure 3 |
635mm ![]() |
XB
|
205mm 89mm |
XB
|
205mm
x32mm |
Note: All units are shown with optional thermostat kit installedThermostat well with sensing bulb |
|