.jpg)
DSU Series
Destratification Units
Application
These energy saving units are designed to reduce the cost of heating a building by recycling warm air that has collected at high level. They are for use in industrial premises such as factories and warehouses and are effective at mounting heights between 4m and 12m. Typically they would be used in conjunction with BN Thermic OUH unit heaters. Depending on the ceiling height, a reduction of heating costs of up to 30% is possible.
Features
- Robust industrial quality case
- 4-way adjustable louvres
- Built-in thermostat to activate fan when a high air temperature is detected
- Supplied with suspension kit comprising 4 x 500mm chains each with 2 x musket hooks
- Ingress protection to IP44
Specification
| Model | Volts |
Airflow (m³/h)
|
Dimensions |
Weight (kg) |
||||
|---|---|---|---|---|---|---|---|---|
| H | W | D | ||||||
| DSU-4 | 230 | 4000 | 385 | 560 | 560 | 18 | ||
| DSU-8 | 230 | 8000 | 385 | 720 | 720 | 24 | ||
| Model | Mounting Height |
Area covered by one unit |
|---|---|---|
| DSU-4 | 4m to 7m | 20m x 20m |
| DSU-8 | 7m to 12m | 25m x 25m |
For example a building 40m x 40m x 6m high should be divided into 4 sections with a DSU-4 mounted centrally in each section.