Range & Prices

The prices shown are list prices and perfectly safe to use for budget purposes. Contact your electrical wholesaler for final prices.

Heaters

Model kW Volts Built-in Thermostat List Price
SCHG-30 3 230 No £228.00
SCHG-30T 3 230 Yes £303.00
SCHG-45 4.5 230 No £270.00
SCHG-45T 4.5 230 Yes £342.00
SCHG-60 6.0 230 No £378.00
SCHG-60T 6.0 230 Yes £460.00
AN SCH fan heater provides simple and reliable heating in a car service reception area

An SCH fan heater provides simple and reliable heating in a car service reception area

Heater specifically designed for integration into a suspended ceiling grid

Heater specifically designed for integration into a suspended ceiling grid

Controls

Each heater can be controlled by one wall-mounted controller and/or one thermostat

Do not use room thermostat with ‘T’ suffix models as these heaters already have a built-in thermostat.

Type Description Model List Price
Switch On/off/high heat/low/heat/fan only CS-7 £60.00
Thermostat Adjustable room thermostat RST2-IN  £74.00
Thermostat Tamperproof room thermostat RST-TP  £80.00

Technical Specification

Colour: Exposed surfaces white RAL9016
Other surfaces zinc plated steel
Finish:   Epoxy polyester powder coating
Construction: 0.9mm steel case
Aluminium air diffuser in brilliant white
Fan Assembly: Tangential fan with low noise aluminium fan blades
Shaded pole high performance motor
Factory lubricated bearings (servicing not required)
Heating Element: High quality nickel-chrome resistance wire supported by ceramic plates and fitted with an automatically resetting over-temperature device
Control (models with built-in thermostat)

Temperature control by factory fitted electronic thermostat with panel front adjustment

Default mode – built-in thermostat switches heat and fan.  This can be changed so thermostat switches heat only with fan running continuously.

Can be controlled by CS-7 wall mounted controller for on/off/high heat/low heat and fan only settings

Control (models without built-in thermostat)

Temperature control can be provided by a room thermostat

Can be controlled by CS-7 wall mounted controller for on/off/high heat/low heat and fan only settings.  CS-7 can be used in conjunction with a room thermostat

Installation: Designed to rest in the T-bar of a 600 x 600 suspended ceiling grid
Recommended mounting heights 2.5m to 4m above floor level (see table below)
Guarantee: 1 year

 

Physical data

Model Width (mm) Depth (mm) Height (mm) Required clearance
above grid (mm)
Weight (kg)
SCHG-30(T) 576 592 153 200 9
SCHG-45(T) 576 592 153 200 10
SCHG-60(T) 576 592 152 200 13
SCH heater installed in a school outfitters

SCH heater installed in a school outfitters

Performance Data

Model kW Volts Airflow (m³/h)   dB* @2m Mounting Height (m)
SCHG-30(T) 3 230 245 56 2.4 to 3.0
SCHG-45(T) 4.5 230 370 60 3.0 to 4.0
SCHG-60(T) 6.0 230 490 58 2.4 to 3.0

* Noise levels are factory tested, not laboratory tested.

 

Spare Components

This is a list of the more frequently requested spare components.  Should you require a component that is not listed, please contact BN Thermic.

Part No Description
90016 Egg-crate grille (white)
AS-SCH-30 Fan/motor/element assembly (3kW) – two used in 6kW heater
AS-SCH-45 Fan/motor/element assembly (4.5kW)

Selection

If you would like the experts at BN Thermic to select a suitable heating for your application, please click below to access our enquiry form.  Simply provide as much information as you have available and we will respond with a detailed proposal.

Enquiry Form

In simple terms the output of the SCH heater or heaters must be greater than the heat losses from the building during periods of cold weather.  A small amount of heat is lost through the walls, ceilings and floors with more significant losses through windows and doors.

To estimate the heat loss from your building you may like to use our heat calculation tool

Heat Calculator

The estimated heat loss figure is the absolute minimum kW output that you should consider installing.  We would suggest adding approximately 50% to this figure to allow for an acceptable warm up time in cold conditions as well as making allowances for exceptional weather conditions and possible errors in the original data used in the estimate.

The next step is to select the output of the heater(s) taking into consideration the height of the suspended ceiling.  Use the following table as a guide.

Model kW Built-in Thermostat Recommended mounting height (m)
SCHG-30 3.0 No 2.4 to 3.0
SCHG-30T 3.0 Yes 2.4 to 3.0
SCHG-45 4.5 No 3.0 to 4.0
SCHG-45T 4.5 Yes 3.0 to 4.0
SCHG-60 6.0 No 2.4 to 3.0
SCHG-60T 6.0 Yes 2.4 to 3.0

Having established the minimum kW output required and the ouput of the individual heater(s), select the minimum number of heaters needed to meet the kW requirement.