- Control up to 12 industrial fan heaters from a single point – ideal for warehouses
- All connections by Cat5 cable for super quick and error free installation
- Can be connected to any heater in the System X range – any combination – any sequence
Range & Prices
The prices shown are list prices and perfectly safe to use for budget purposes. Contact your electrical wholesaler for final prices.

Multiple 25kW heaters daisy chained with Cat5 cable. A quick and easy install with no connection errors
Model Number | kW | List Price |
XH03 | 3.0 | £1250.00 |
XH05 | 5.0 | £1265.00 |
XH10 | 10 | £1320.00 |
XH15 | 15 | £1771.00 |
XH20 | 20 | £1877.00 |
XH25 | 25 | £1936.00 |
Control Components |
|||
Type | Description | Model |
List Price |
Controller | With thermostat On/off/high/low/fan only settings Open window detection |
CX1 |
£137.00 |
Controller | With tamper resistant thermostat On/off/high/low/fan only settings Open window detection |
CX2 |
£140.00 |
Controller | Without thermostat On/off/high/low/fan only settings |
CX3 |
£139.00 |
Controller | With digital programmable thermostat Optimum start feature |
CX6 |
£241.00 |
Controller | For use with volt-free signal from BMS (for 230V signal a VI Interface is required) | CX-BMS |
£131.00 |
Sensor | Optional remote sensor for use with CX1, CX2 or CX6 | CXS |
£39.00 |
Cable | Cat5 terminated 5m | DX05 |
£9.00 |
Cable | Cat5 terminated 10m | DX10 |
£14.50 |
Cable | Cat5 terminated 20m | DX20 |
£22.00 |
Joiner | Cat5 cable joiner | JX1 |
£5.00 |
How it Works
System X industrial fan heaters provide comfort or background heat in a wide variety of industrial buildings such as warehouses and factories.
A system will include a controller and up to 12 individual heaters. The control daisy chain is connected using Cat5 cables ensuring the quickest possible installation time. Power is introduced to each heater individually with the controller taking its power from the first heater in the chain.
A unique feature of System X is that any style of heater from the range can be incorporated into a control daisy chain. For example, an air curtain could be added to an industrial fan heater system. Heaters can be connected in any combination and any sequence.

Four industrial fan heaters controlled from a single controller
Technical Specification
Colour: | Light grey case with black grille and bracket |
Finish: | Epoxy polyester powder coating |
Construction: | 1.2mm steel case |
Fan: | Motor mounted in cool compartment |
Thermally protected motor | |
Totally enclosed and factory lubricated fan motor | |
Protection Devices: | High-limit temperature control with automatic reset |
Heat purge device clears residual heat | |
Heating Element: | Stainless steel sheathed tubular heating element |
Concentric formation for optimum heat transfer | |
Control: | Up to 12 heaters can be connected to a single controller in any combination or sequence. Control connections are by Cat5 cable |
Installation: | Specially designed bracket, foe ceiling or wall mounting, provides a variety of discharge angles and 360﮿ rotation |
Suspension hooks are supplied as standard | |
Max air temperature: | 30°C |
Guarantee: | 5 year (assuming standard comfort heating application) |
Performance Data |
|||||||
Model | kW | Volts | Airflow (m³/h) | Approximate Temperature Rise ( ﮿C) | dB*@2m |
Max Recommended Mounting Height (m) |
|
Horizontal Discharge | Vertical Discharge | ||||||
XH-03 | 3.0 | 230V/1 or 400V/3N | 1100 | 7 | 60 | 2.5 | 3.0 |
XH-05 | 5.0 | 230V/1 or 400V/3N | 1100 | 13 | 60 | 2.5 | 3.0 |
XH-10 | 10 | 400V/3N | 1100 | 25 | 60 | 2.5 | 3.0 |
XH-15 | 15 | 400V/3N | 3150 | 13 | 65 | 3.0 | 3.5 |
XH-20 | 20 | 400V/3N | 3150 | 17 | 65 | 3.0 | 3.5 |
XH-25 | 25 | 400V/3N | 3150 | 22 | 65 | 3.0 | 3.5 |
* Noise levels are factory tested, not laboratory tested.
Physical Data
kW | Height (mm) | Width (mm) | Depth (mm) | Weight (kg) |
3 to 10 | 320 | 435 | 405 | 18 |
15 to 25 | 445 | 565 | 485 | 37 |

25kW heater providing comfort heat in a warehouse in Kent
Technical Specifications – Controls
MODEL: CX1
Maximum number of heaters controlled: 12
Type of heaters controlled: any heaters from the System X range in any sequence
Electrical Supply: taken from heater via Cat5 cable
Heater settings: on/off/high heat/low heat/fan only
Built-in adjustable thermostat range: 0 to 30˚C
Connection to first heater in group: Cat5 cable
Mounting: surface mount
Dimensions: 120mm x 80mm x 40mm
Special Feature: Open window detection (user selectable)

Model: CX2
As CX1 but with a tamper resistant built-in thermostat

Model: CX3
As CX1 but without built-in thermostat or open window detection

Model: CX6
As CX1 but with:
7-day programmable timer
Temporary override
Temporary lock
Optimum start for enhanced economy (user selectable)
Without open window detection

Model: CX-BMS
As CX1 but without manual or thermostat control
Requires a volt-free signal from a BMS to switch heater on and off
Can operate with a 230V signal via a VI Interface
Model: CXS
Remote mounted sensor for use with CX1, CX2 or CX6 controller
Overrides the controller’s built-in air sensor
Recommended maximum cable length between controller and sensor: 20m
Mounting: surface mount
Dimensions: 80mm x 80mm x 35mm
Pre-terminated Cat5 Cables
DX05: 5m
DX10: 10m
DX20: 20m
JX1: Cat5 Joiner / Coupler – Click fit (Joins two Cat5 cables together should you require longer lengths)
Selection
If you would like the experts at BN Thermic to select a suitable heating for your application, please click here to access our enquiry form. Simply provide as much information as you have available and we will respond with a detailed proposal.
In simple terms the combined output of the heaters must be greater than the heat losses from the building during periods of cold weather. A small amount of heat is lost through the walls, ceilings and floors with more significant losses through windows and doors.
To estimate the heat loss from your building you may like to use our heat calculation tool
The estimated heat loss figure is the absolute minimum kW output that you should consider installing. We would suggest adding approximately 50% to this figure to allow for an acceptable warm up time in cold conditions as well as making allowances for exceptional weather conditions and possible errors in the original data used in the estimate.
Having established the minimum kW output, select the minimum number of heaters needed to meet this requirement. The heaters should be evenly distributed.
When ceiling heights exceed 4m, we strongly recommend the use of destratification units. These devices will reduce heating costs by recycling warm air that has collected at high level.
Videos
Images
- XH SystemX industrial fan heater with CX-1 controller
- OUH3-3W Industrial Fan heater front view showing heating elements
- OUH3-3W Industrial Fan Heater
- XH SystemX industrial fan heater rear view showing Cat5 connection
Installation images
- SystemX - Quick, multiple heater installations with zero connection errors
- Two 25kW heaters daisy chained with Cat5 cable in an industrial application
- XH industrial fan heaters are hand assembled in the UK and backed with a 5 year warranty
- 25kW heater providing comfort heat in a warehouse in Kent
- XH Industrial fan heaters are ideal for frost protection in large buildings
Downloads